Attic Ventilation Calculator

Work out the net free vent area your attic needs (1/150 or 1/300 of the attic floor area) and split it between intake (eave) and exhaust (ridge) vents.

The floor or ceiling area under the roof that is being vented. For a flat ceiling this is about the footprint of the house.
The IRC requires 1/150, with a 1/300 exception under the conditions named. Code editions word the exception differently, so confirm with your local building department.
%
Vents at or near the ridge. The rest goes low at the eaves or soffit (intake). The IRC exception for 1/300 needs 40–50% high; DOE advises no more than 50% high.

Results

Total net free vent area needed
1,209.6
Attic area ÷ 150. Use the net free area printed on each vent, not its overall size.
Low vents (intake: eave, soffit)
604.8
High vents (exhaust: ridge, roof)
604.8
Keep upper vents within 3 ft of the ridge where possible.

Estimate only. This tool is for informational and educational purposes. Results depend on your inputs and simplifying assumptions, and are not a substitute for professional engineering, design or financial advice. Always verify with a qualified professional and applicable codes before purchasing, building or making decisions.

How it’s calculated

Building codes size attic ventilation by net free area, the clear open area of a vent after allowing for screens and louvers. The International Residential Code (R806.2) sets the minimum at 1/150 of the area of the vented space, and permits 1/300 where a vapor retarder is installed on the warm side of the ceiling in cold climate zones (6, 7 and 8) or where 40 to 50 percent of the area is in upper vents with the rest at the eaves. Ventilation should be balanced between low intake and high exhaust vents.

Total net free area = attic floor area ÷ 150 (or ÷ 300) High vents = total × high share; low vents = total − high vents 1 ft² = 144 in²

Example (U.S. Department of Energy guideline): a 30 ft × 42 ft house has 1,260 ft². At 1/300 the attic needs 1,260 ÷ 300 = 4.2 ft² = 605 in², about half (303 in²) of it high on the roof and the rest at the eaves. At 1/150 it needs 8.4 ft² = 1,210 in².

Check the net free area stated on the vent's label: screened vents can be around 60 percent free. Code editions differ in how they word the 1/300 exception, and some regions adopt their own rules, so confirm with your local building department. Spray-foamed and other unvented roofs follow different rules.

Frequently asked questions

How much attic ventilation do I need?

The IRC minimum is 1 square foot of net free vent area per 150 square feet of attic floor, or per 300 square feet where the code exception applies. That is 144 in² per 150 ft² (0.96 in² per ft²) or half of that.

What is net free area?

It is the clear open area through a vent after screens, louvers and slots reduce the opening. Manufacturers print it on the vent or its data sheet.

How should I split intake and exhaust?

The IRC 1/300 exception puts 40 to 50 percent of the area in upper vents (within 3 ft of the ridge) and the rest at the eaves. DOE guidance also says no more than about half should be high on the roof.

Does this apply to a vaulted ceiling or a roof with no eaves?

Roofs with no soffit or eave openings need the larger 1/150 area according to DOE guidance, and rafter spaces use the sloped ceiling area. Ask your building department about special cases.

Embed this calculator

Add this free calculator to your own website. Copy the code below into your page’s HTML:

Need this calculator branded, changed or built around your own prices?See custom business solutions →

Sources

Formulas are taken from the free public references above. Results are provided “as is” for informational and educational purposes only. See our disclaimer.

Added · Last updated · How we check our calculators

Spotted a mistake or missing option? Report a problem· Suggest a calculator