Voltage Drop Calculator

Voltage drop and percent drop for copper or aluminum conductors by AWG/kcmil size, length and current, single-phase or three-phase.

V
Single-phase: line voltage (e.g. 120, 240). Three-phase: line-to-line (e.g. 208, 480).
A
Areas from the AWG definition in NBS Handbook 100 (solid-conductor equivalent).
Resistance rises about 0.39% per °C. 75 °C is a common conductor rating; use 20 °C for a cold conductor.

Results

Voltage drop
6.01 V
Percent drop
5.01 %
Above 5%: consider a larger conductor.
Voltage at the load
114.0 V
Conductor resistance
1.8796 Ω per 1000 ft
6.1665 Ω/km
Conductor cross-section
3.309
6530 circular mils
Power lost in conductors
96.2

Estimate only. This tool is for informational and educational purposes. Results depend on your inputs and simplifying assumptions, and are not a substitute for professional engineering, design or financial advice. Always verify with a qualified professional and applicable codes before purchasing, building or making decisions.

How it’s calculated

Each conductor’s resistance is R = ρL/A. Current flows out and back, so a single-phase (or DC) circuit drops voltage across two conductor lengths. In a balanced three-phase circuit the line-to-line drop is √3 times the drop in one conductor. Resistivity is corrected for temperature with ρ = ρ₂₀[1 + α(T − 20 °C)].

R (one conductor) = ρ × L / A Single-phase / DC: Vd = 2 × I × R Three-phase: Vd = √3 × I × R % drop = Vd / V × 100

Assumptions: resistance only (reactance and power factor neglected, which is reasonable for smaller conductors and short runs), solid-conductor cross-section, uniform temperature. Stranded and large conductors, conduit material and power factor change the real drop; NEC Chapter 9 Table 9 gives AC impedance values.

Example: 16 A at 120 V over 100 ft of 12 AWG copper at 20 °C. 12 AWG = 0.0808 in = 3.31 mm²; R per conductor = 1.68 × 10⁻⁸ × 30.48 ÷ 3.31 × 10⁻⁶ = 0.155 Ω, so Vd = 2 × 16 × 0.155 = 4.95 V (4.1%). At 75 °C the drop rises to about 6.0 V (5.0%).

The National Electrical Code’s informational notes suggest limiting voltage drop to about 3% for a branch circuit and 5% for feeder plus branch combined. Conductor ampacity is a separate, mandatory check.

Frequently asked questions

What is an acceptable voltage drop?

A widely used guideline (NEC informational notes) is 3% on a branch circuit and 5% total for feeder plus branch. These are recommendations for efficiency and performance, not ampacity limits.

Should I use one-way or round-trip length?

Enter the one-way distance from the source to the load. The calculator applies the factor of 2 (single-phase) or √3 (three-phase).

Why does aluminum drop more voltage?

Aluminum’s resistivity (2.65 × 10⁻⁸ Ω·m) is about 1.6 times copper’s (1.68 × 10⁻⁸ Ω·m), so an aluminum conductor needs to be about two AWG sizes larger for the same drop.

Can I use this to choose a wire size?

Only for the voltage-drop part. Wire size must also satisfy ampacity, temperature rating, overcurrent protection and local code. Have an electrician or engineer confirm.

Embed this calculator

Add this free calculator to your own website. Copy the code below into your page’s HTML:

Sources

Formulas are taken from the free public references above. Results are provided “as is” for informational and educational purposes only. See our disclaimer.

Spotted a mistake or missing option? Report a problem · GitHub issue· Suggest a calculator