Wire Gauge (AWG) to mm² Converter

Convert AWG wire sizes (4/0 to 40) to diameter in mm and inches, cross-section in mm² and kcmil, or find the nearest AWG for a given mm² or diameter.

4/0 (also written 0000) is the largest standard size, 40 the smallest. A larger number means a thinner wire.

Results

diameter
2.053
cross-section
3.309
cross-section in kcmil
6.53 kcmil
kcmil = thousand circular mils (MCM).
Note
This converts wire size only. It is not an ampacity (current rating) table: sizing wire for current needs your local electrical code and a qualified electrician.

How it’s calculated

American Wire Gauge (AWG) sizes follow a geometric rule fixed by the ASTM B258 standard: 36 AWG is defined as 0.0050 inch and 4/0 (0000) as 0.4600 inch, with 39 equal-ratio steps between them. Each step down in gauge number makes the wire about 12.3% thicker; every 6 gauge numbers doubles the diameter and every 3 doubles the area.

diameter (in) = 0.005 × 92^((36 − n) ÷ 39) (n = 36 for 36 AWG, 0 for 1/0, −1 for 2/0, −2 for 3/0, −3 for 4/0) diameter (mm) = diameter (in) × 25.4 area (mm²) = π ÷ 4 × diameter (mm)² circular mils = (diameter in mils)², 1 kcmil = 1,000 cmil = 0.5067075 mm² gauge from diameter: n = 36 − 39 × ln(d ÷ 0.005 in) ÷ ln(92)

Example: 12 AWG. 92^(24 ÷ 39) = 16.163, so the diameter is 0.005 × 16.163 = 0.0808 in = 2.053 mm. Area = π ÷ 4 × 2.0525² = 3.309 mm², which is 6.53 kcmil. Going the other way, a 2.5 mm² conductor has a diameter of 1.784 mm, which is gauge 13.2. The nearest size is 13 AWG (2.624 mm², 5.0% larger). If the gauge number comes out as 13.6, the nearest size is 14 AWG (thinner) while the smallest size at least as large is 13 AWG.

Results use the exact formula. Published AWG tables round diameters slightly (to 0.1 mil), so the last digit can differ. The sizes are for solid round conductors; stranded wire of the same gauge has a similar copper area but a larger overall diameter.

Not an ampacity table. How much current a wire may carry depends on insulation, temperature, bundling, length and local rules. Sizing wire for current needs your local electrical code and a qualified electrician.

Frequently asked questions

What is 12 AWG in mm²?

12 AWG has a diameter of 2.053 mm and a cross-section of 3.309 mm². Metric cable is usually sold as 4 mm², the nearest standard size above it.

How do I convert mm² to AWG?

Find the diameter from the area (d = √(4A ÷ π)), then use n = 36 − 39 × ln(d ÷ 0.127 mm) ÷ ln 92. This calculator does it and shows the nearest AWG and the smallest size that is at least as large.

Why is a higher AWG number a thinner wire?

The gauge originally counted the number of times a wire was drawn through smaller dies, so more draws meant a thinner wire. 4/0 is the thickest standard size and 40 the thinnest.

Can I choose a wire size for a circuit with this?

No. This only converts between size systems. The current a wire can safely carry depends on its insulation, installation and your local electrical code, so ask a qualified electrician.

Embed this calculator

Add this free calculator to your own website. Copy the code below into your page’s HTML:

Need this calculator branded, changed or built around your own prices?See custom business solutions →

Sources

Formulas are taken from the free public references above. Results are provided “as is” for informational and educational purposes only. See our disclaimer.

Added · Last updated · How we check our calculators

Spotted a mistake or missing option? Report a problem· Suggest a calculator